Vol 6 No 7 (2022): Volume 6, Issue 7, July 2022 | Pages: 12-15
International Research Journal of Innovations in Engineering and Technology
OPEN ACCESS | Research Article | Published Date: 04-07-2022
This study examines the performance of split-type air conditioning with a cooling capacity of 1 PK after replacing a less environmentally friendly refrigerant with a more environmentally friendly one, ranging from R32 to R1270. R1270 has a mass of 50%. The evaporator's inlet temperatures are 23°C, 25°C, and 27°C, while the condenser's inlet temperatures are 30°C and 35°C. The results showed that there was a 41.47 percent decrease in power consumption from R32 to R1270 for cooling capacity, and a 45.46 percent decrease from R32 to R1270 for heating capacity. From R32 to R1270, the COP value decreased by 19.04 percent. R32 still outperforms R1270 in terms of performance, but R1270 has lower power consumption, making electricity consumption more efficient.
Energy Conversion, Air Conditioning, R32, R1270
Ridwan, Berkah Fajar, Tony Suryo Utomo, “Experimental Study of Performance AC Split R32 Retrofited with R1270 on 50% Mass” Published in International Research Journal of Innovations in Engineering and Technology - IRJIET, Volume 6, Issue 7, pp 12-15, July 2022. Article DOI https://doi.org/10.47001/IRJIET/2022.607003