Water
chiller is a crucial air conditioning unit in various industries, tasked with
efficiently cooling large spaces. It utilizes two refrigerants, primary and
secondary, during its cooling process. A well-functioning air conditioning
system not only ensures human comfort but also benefits machinery and the
overall environment. However, one significant issue leading to excessive
electricity consumption is the mismatch between the refrigeration system's
initial design and its real-world operation. To ensure energy efficiency, it's
essential to evaluate the chiller's performance meticulously. To analyze the
water chiller's performance, data was collected from its control panel over
three days. This data includes water pressure and temperature both entering and
exiting the evaporator, set point ampere, and compressor power. With this data,
the actual Coefficient of Performance (COP) can be calculated and compared
against the design COP. The research findings reveal that between January 23,
2023, and January 25, 2023, the chiller's actual COP falls below the design COP
at 05:00, 08:00, 11:00, and 21:00. However, at 23:00, the actual COP surpasses
the design COP. In conclusion, the water chiller demonstrates less efficient
cooling during specific hours, resulting in heightened energy consumption.
Country : Indonesia
IRJIET, Volume 7, Issue 11, November 2023 pp. 14-21