Impact Factor (2025): 6.9
DOI Prefix: 10.47001/IRJIET
With the
ever increasing number and capacities of the distributed generations
(DGs)penetrating the conventional radial electrical power distribution
networks, there is need for a detailed assessment on the impacts the DGs have
on the distribution network’s sequence impedances during fault conditions. The
conventional distribution networks are designed to extract power from the
transmission network and distribute it to the loads. The distribution networks were
not designed to have DGs directly connected into them hence their power flow is
unidirectional from the main utility grid to the loads. When balanced,
un-faulted and in normal operating state, the power system’s voltages and
currents can be evaluated and determined with utmost simplicity. When the power
systems is balanced and un-faulted, the line and phase for both the voltages
and the currents are of equal magnitudes and displaced by 120º from each other,
however, when the power system network is unbalanced and faulted, the
magnitudes of the phase voltages and currents are not equal and are displaced
by angles more or less than 120º, hence evaluating and determining the network
quantities can be difficult under the unbalanced and faulted operating
conditions.
During a
fault, a simplified approach to the evaluation of the network voltages and
currents can be achieved by use of symmetrical components theory which proposes
that for any set of unbalanced currents occurring in an electrical network, a
set of three balanced currents namely the positive sequence currents, the
negative sequence currents and the zero sequence currents can be developed and
used to simplify the solution to the unbalanced phase voltages and currents.
The flow of the three set of symmetrical currents gives rise to a set of three
symmetrical voltages namely the positive, negative and zero sequence voltages.
The impedance offered by each power system equipment to the flow of the
symmetrical sequence currents are respectively referred to as the positive
sequence impedances, the negative sequence impedances and the zero sequence
impedances.
Wind
turbine generators (WTGs) are one of the most common renewable energy dependent
DG technologies largely integrated into the distribution networks. These WTGs
are interfaced into the distribution networks either through induction or
synchronous machines with the two generator technologies broadly classified as
the doubly fed induction generator (DFIG) and the Type IV WTG technologies. An
important aspect of the DFIG and the Type IV WTG studies is to evaluate their
impacts on the positive, negative and zero sequence impedances of a
distribution network under different short circuit conditions. For purposes of
this paper, the IEEE 13 node radial test feeder was modelled for the short
circuit study in electrical transient analysis program (ETAP) software. The
short circuit study was then performed on the radial test feeder firstly
without WTGs connected and secondly with DFIGs and Type IV WTGs interchangeably
connected at NODE650, NODE632, NODE671 and NODE680 of the radial test feeder. This
paper presents a detailed investigation on the impacts the DFIG and the Type IV
WTG with their capacities being increased from 1MW to 3MW have on the positive,
the negative and the zero sequence reactance of NODE650, NODE632, NODE671 and
NODE652 of the IEEE 13 node radial test feeder during a short circuit.
Country : Kenya
IRJIET, Volume 7, Issue 2, February 2023 pp. 1-15