Transient Effectiveness Test of Cross Flow Air Heater Heat Exchanger

Abstract

The problem of high electrical energy consumption in HVAC (heating, ventilation, and air conditioning system), makes renewable energy a solution to the problem. Renewable energy sources such as solar, geothermal, and wind energy are used in reducing electrical energy consumption, which is functioned to warm the room (space heating), drying agricultural products, melting snow-filled roads, heating agricultural land (soil heating), greenhouse heating, and hot springs. heat exchanger is a heat conducting device that can transfer energy from a fluid with a hot temperature to a cold temperature fluid or vice versa which can be used in the application of drying products produced by farmers, plantations, and large or small scale fisheries. Due to the function of the heat exchanger as a room heater, an effectiveness performance test was carried out on the air heater heat exchanger research carried out at the Thermofluid Lab, Department of Mechanical Engineering, Diponegoro University. In this test, several variations of water flow rate and air speed were carried out. There are variations of water flow discharge of 5 liters/minute, 2.5 liters/minute, and 0 liters. In the variation of air velocity there are speeds of 3.6 m/s, 2.7 m/s, and 1.8 m/s. The analysis obtained in the study is that the greatest effectiveness value occurs in the variation of water flow discharge of 2.5 liters/minute with an air speed of 1.8 m/s with a maximum effectiveness value of 0.622 and a minimum of 0.521.

Country : Indonesia

1 Muchammad2 Akmal Hafidh Purnomo3 Budi Setiyana

  1. Mechanical Engineering Department, Faculty of Engineering, Diponegoro University, Jl. Prof. H. Soedarto, SH, Tembalang-Semarang 50275, Indonesia
  2. Mechanical Engineering Department, Faculty of Engineering, Diponegoro University, Jl. Prof. H. Soedarto, SH, Tembalang-Semarang 50275, Indonesia
  3. Mechanical Engineering Department, Faculty of Engineering, Diponegoro University, Jl. Prof. H. Soedarto, SH, Tembalang-Semarang 50275, Indonesia

IRJIET, Volume 9, Issue 4, April 2025 pp. 156-160

doi.org/10.47001/IRJIET/2025.904023

References

  1. Azwinur and Zulkifli (2019) 'Experimental Study of the Effect of Baffles on Tools', journal synthesis: Scientific Journal of Mechanical Engineering, 13(1), pp. 8–14.
  2. Darliansyah, I. (2005) 'Performance Evaluation of Heat Exchanger 11E-25 in the Preheating Section in the Crude Distilling Unit at PT Pertamina (Persero) Refinery Unit IV Cilacap', Hilos Tensados, 1, pp. 1–476.
  3. Juliartha, I.G.L.R., Mirmanto and Okariawan (2018) 'The Effect of Massflow and Hot Water Temperature in Parallel Pipe Heat Exchangers on Heat Transfer Rates in Heating Rooms', Journal of Mechanical Engineering, 1(1), pp. 1–16. Available at: http://eprints.unram.ac.id/id/eprint/5266.
  4. Pandey, F., Kuntjoro, Y.D. and Uksan, A. (2022) 'Space Heating System Planning by Utilizing Heat Energy from Brine at Wayang Windu Geothermal Field', Citizenship Journal, 6(2), pp.2836–2846. Available at: http://journal.upy.ac.id/index.php/pkn/article/view/3166.
  5. Qin, D., Liu, J. and Zhang, G. (2021) ‘A novel solar-geothermal system integrated with earth–to–air heat exchanger and solar air heater with phase change material—numerical modelling, experimental calibration and parametrical analysis’, Journal of Building Engineering, 35(October 2020), p. 101971. Available at: https://doi.org/10.1016/j.jobe.2020.101971.
  6. Ratnawati, R. and Salim, A. (2018)'Redesign of Shell 52 and Tube Type Heat Exchanger Using Carbon Steel and Stainless Steel 304 Tube Materials', Turbo: Journal of the Mechanical Engineering Study Program, 7(1), pp. 74–80. Available at: https://doi.org/10.24127/trb.v7i1.712.
  7. Robiyanyusra, Gani, U.A. and Taufiqurrahman, M. (2021) 'Analysis of the Effectiveness of the Heat Transfer Rate of a Double Pipe Type Heat Exchanger', Journal of Mechanical Engineering Technology (JTRAIN), 2(2), pp. 97–104.
  8. S, R.M. and Ghofur, A. (2019)'Performance Analysis of Primary Air Heater (Pah) Pltu Asam Asam Unit I - South Kalimantan', Jtam Rotary, 1(2), p. 173. Available at: https://doi.org/10.20527/jtam_rotary.v1i2.1747.
  9. Sinaga, A. (2019)'The Effect of Air Heaters on Increasing Boiler Efficiency in Unit 3 of Pt Pt. Pln (Persero) Belawan Generation Implementation Unit.', Mechanical Engineering, pp. 1–78.
  10. Tambunan, J.F. (2016) Fluid Temperature Control in Heat Predictive Control (Gpc).